HERD
-
There is increasing need to perform invasive surgical procedures in intensive care units (ICUs). Traditional ICUs differ from operating rooms (ORs) in several ways including air changes per hour (ACH) and pressurization. Increased ACH and positive pressurization of ORs intend to provide more aseptic environments for surgery. Development of procedure ready ICUs that transition through unoccupied, occupied, and procedure modes is one solution to improve environmental quality when performing surgery in ICUs. This study assessed the efficacy of two airflow control systems, variable air volume (VAV) and Venturi control, in preventing contaminants from entering ICU from adjacent corridors. ⋯ Using efficient mode transitioning systems in ICUs may be effective in creating a more aseptic environment that mimics that of the OR.